Refrigerant Cylinder Safety

Did you know that refrigerant recovery cylinders have different pressure ratings and maximum filling capacities? It is unsafe to collect refrigerants into cylinders with the incorrect pressure rating or to overfill a cylinder, even if it is in the correct cylinder type for its pressure.

DOT & EPA Compliance of Refrigerant Recovery

  • The recovery weight shall NOT exceed 80% of the recovery cylinder capacity for non-flammable refrigerants

  • The pressure of the refrigerant at 131°F shall not exceed 5⁄4 of the cylinder’s service pressure for non-flammable refrigerants

To comply with these requirements and for the safety of our technicians (and yours), A-Gas will not accept refrigerant in overfilled cylinders or cylinders that do not meet the required service pressure of the refrigerant recovered.

Please verify the weight recovered in each cylinder and each cylinder's required refrigerant service pressure against the provided Non-Flammable Refrigerant Maximum Net Recovery Weights Chart (Document #251) and Flammable Refrigerant Maximum Net Recovery Weights Chart (Document #754).

This information is believed to be accurate and reliable, but is provided for guidance only. A-Gas accepts no responsibility, and the user assumes all risks and liability for use of this information.

identifying certified recovery cylinders infographic thumbnail

Identifying DOT-Certified Recovery Cylinders

Counterfeit recovery cylinders look similar to legitimate DOT-certified cylinders but lack rigorous testing and construction standards. They pose a significant threat to safety, the environment, compliance, and the industry. Download the infographic, which is also accessible in our Cylinder Program Guide. You can learn more about the importance of using a certified recovery cylinder in this article.

The industry has seen counterfeit cylinders from a few brands. If you have a cylinder in question, contact us or your A-Gas representative directly.

Identifying A2L Recovery Cylinders

A2L refrigerant recovery cylinders have key differences from traditional ones. This infographic shows the differences between the two and what options you could consider if you do not have A2L refrigerant recovery cylinders on hand. 

Remember to only use recovery tools rated for A2Ls with A2L refrigerants and never exceed fill limits. 

A2L recovery cylinder infographic
safe cylinder checklist thumbnail

Safe Cylinder Checklist

Health and safety are at the heart of everything we do, and we are committed to demonstrating best practice across the A-Gas business. Our team put together this Safe Cylinder Checklist to provide a visual guide for our customers and partners, assisting them in doing visual cylinder checks. Download the checklist, which is also accessible in our Cylinder Program Guide.

If you see any defects depicted in the Safe Cylinder Checklist, contact us or your A-Gas representative directly.